Battery Chargers on DIN-Rail with output power from 42W to 480W

based on THF Series of Power Supplies

 

 

 

  • suitable for charging of the maintenance-free sealed lead-acid batteries
  • rectangular constant current-constant voltage charging characteristic curve

 

 

Maximum

Output

Power

Type

Input

Voltage

Range

Charging

Voltage

Charging

Current

Approvals

Dimensions

W x H x D

(mm)

Weight

(kg)

Protections

Note

 

42W

THF45US12-BC

85-264VAC,

120-370VDC

13.8V

3.0A

TUV, UL, CSA, CE

78x93x67

0.30

OVP, SCP

TP

 

 

 

48W

THF45US24-BC

85-264VAC,

120-370VDC

27.2V

1.7A

TUV, UL,  CSA, CE

78x93x67

0.30

OVP, SCP

TP

 

 

 

76W

THF75US12-BC

85-264VAC,

120-370VDC

13.8V

5.5A

TUV, UL, CSA, CE

55.5x125.2x100

0.55

OVP, SCP

TP

 

 

 

77W

THF75US24-BC

85-264VAC,

120-370VDC

27.2V

2.8A

TUV, UL, CSA, CE

55.5x125.2x100

0.55

OVP, SCP

TP

 

 

 

77W

THF75US48-BC

85-264VAC,

120-370VDC

54.0V

1.4A

TUV, UL, CSA, CE

55.5x125.2x100

0.55

OVP, SCP

TP

 

 

 

120W

THF120LS12-BC

88-132VAC,

176-264VAC,

248-370VDC

13.8V

8.7A

TUV, UL,  CSA, CE

65.5x125.2x100

0.65

OVP, SCP

TP

 

 

 

120W

THF120LS24-BC

88-132VAC,

176-264VAC,

248-370VDC

27.2V

4.4A

TUV, UL,  CSA, CE

65.5x125.2x100

0.65

OVP, SCP

TP

 

 

 

120W

THF120LS48-BC

88-132VAC,

176-264VAC,

248-370VDC

54.0V

2.2A

TUV, UL,  CSA, CE

65.5x125.2x100

0.65

OVP, SCP

TP

 

 

 

240W

THF240PS24-BC

85-264VAC,

120-370VDC

27.2V

8.8A

TUV, UL,  CSA, CE

125.5x125.2x100

1.10

OVP, SCP

TP

PFC

 

 

240W

THF240PS48-BC

85-264VAC,

120-370VDC

54.0V

4.4A

TUV, UL,  CSA, CE

125.5x125.2x100

1.10

OVP, SCP

TP

PFC

 

 

480W

THF480PS24-BC

180-264VAC,

250-370VDC

27.2V

17.6A

TUV, UL,  CSA, CE

227x125.2x100

2.40

OVP, SCP

TP

PFC

 

 

480W

THF480PS48-BC

180-264VAC,

250-370VDC

54.0V

8.8A

TUV, UL,  CSA, CE

227x125.2x100

2.40

OVP, SCP

TP

PFC

 

 

LEGEND:

Protections: OVP=Overvoltage, SCP=Overcurrent, TP=Overtemperature, PFC=Power Factor Correction (in accordance with EN 61000-3-2)

 

 

 